Input Voltage:
The range of input voltage is from 90~264VAC |
Input Frequency:
47~63Hz |
Input Current:
The maximum input current is 0.65A at 115VAC or 0.32A at 230VAC |
Inrush Current:
The cold inrush current will limit less than 50A at 264VAC input voltage |
Load Range:
At factory, the output is checked between 4.9~5.1V(MPE-F40-05)/11.76~12.24V(MPE-F40-12)/23.5~24.5V(MPE-F40-24)/47.04~48.96V(MPE-F40-48) at 60% rated load |
Ripple And Noise:
The peak to peak ripple and noise is less than 50mV(MPE-F40-05)/120mV(MPE-F40-12)/240mV(MPE-F40-24)/480mV(MPE-F40-48). Measuring is done by 20MHz bandwidth limited oscilloscope and terminated each output with a 0.1uF ceramic capacitor and a 10uF electrolysis capacitor at rated load, nominal line |
Line Regulation:
The line regulation is less than +/-0.5% while measuring at rated load and from 100VAC to 240VAC input voltage changing |
Load Regulation:
The load regulation for output is less than +/-1%, measuring is done by changing the output load +/-40% from 60% rated load |
Hold Up Time:
Hold up time is 8mS typical at 115VAC input, full load |
Efficiency:
The efficiency is 78%(MPE-F40-05)/84%(MPE-F40-12)/86%(MPE-F40-24)/88%(MPE-F40-48)typical while measuring is at nominal line and rated load |
Protection:
The power supply will go into hiccup mode against short circuit or over load conditions, and will do auto-recovery while faulty conditions are removed |
Temperature:
0~+50°C (operating); -40~+85°C (storage) |
Humidity:
5~95% non-condensing |
Connectors:
I/P Connector: Molex housing 09-50-3031 and Molex 2878 series cirimp terminal O/P Connector: Molex housing 09-50-3031 and Molex 2878 series cirimp terminal |
Safety:
UL 1950 / TUV EN60950 / CE mark |
EMI:
EN55022 class B |
Dimensions: